← कोर्स पर वापस जाएँ: Spanish Low-Voltage Electrotechnical Regulation (REBT), complete

Final project: brief, submission and assessment

वीडियो जल्द आ रहा है

The time has come to apply the whole course. You must size the electrical installation of a dwelling with data different from the example and submit a design technical memorandum as a document (or PDF) of four to six pages. The goal is not to memorise numbers but to show that you can follow the method and justify each decision with the regulation. When a value depends on a table, cite the current ITC you consulted.

Brief

text
VIVIENDA DEL PROYECTO FINAL
  Casa adosada de 135 m2 útiles en dos plantas
  4 dormitorios, 2 baños + 1 aseo, salón, cocina, lavadero
  Cocina: placa de inducción y horno (5400 W en C3)
  Lavadora, lavavajillas, termo eléctrico y secadora
  Calefacción eléctrica por radiadores en 3 estancias (C8)
  Esquema TT, suministro monofásico, DI de 18 m
  Longitudes cuadro-último punto: C1 35 m, C2 30 m, C3 8 m, C4 10 m, C5 16 m, C8 25 m, C10 12 m

Memorandum requirements

  • 1. Starting data and justified electrification grade.
  • 2. List of circuits (C1-C5 plus any additional ones) with their power.
  • 3. Calculation table: Ib, cross-section, length, voltage drop and breaker per circuit.
  • 4. Individual feeder (cross-section and voltage drop) and IGA.
  • 5. Single-line diagram with grouped RCDs (and justification of the split).
  • 6. Earthing and bathroom: electrode, maximum resistance value, equipotential bonding.
  • 7. Documentation to hand over (certificate, diagram, manual) and planned verifications.

Suggested steps

Start with electrification: with electric heating and more than 100 m² decide the grade and its current (9200 W, 40 A). Continue with the list of circuits and check whether C6 or C7 are needed because of the number of points. Calculate each circuit with the table from the previous lesson; watch C1, at 35 m, where the voltage drop may force you from 1.5 to 2.5 mm². Calculate the 18 m individual feeder and choose its cross-section with margin. Draw the single-line diagram, grouping circuits under RCDs. Finally document earthing, bathroom and verifications.

text
Pistas de verificación (no son la solución completa):
  C1 35 m 6,5 A: con 1,5 mm2 -> e = 2*35*6,5/(48*1,5) = 6,32 V = 2,75 %  (justo; valorar 2,5 mm2)
  C8 calefacción: Ib = P/230; elegir PIA 25 A / 6 mm2 si Ib <= 25 A y comprobar e <= 5 %
  Resistencia de tierra máx. (30 mA, 50 V) = 1667 ohm

Assessment criteria

  • Technical correctness of calculations (Ib, cross-sections, voltage drop, breakers).
  • Consistency between electrification grade, circuits and powers.
  • Correct use of the regulation: ITCs cited and 'consult the current ITC' where appropriate.
  • Clarity of the single-line diagram and table.
  • Safety: RCDs, earthing, bathroom and bonding.

An important reminder: this project is a learning exercise. A real installation must be designed and carried out by an authorised installer company with the documentation required by ITC-BT-04, and the values in this course are indicative. Use it to understand, not to replace consulting the current regulation or the judgement of a competent technician.

If you get stuck, divide the work into one-hour sessions: one for the grade and circuits, another for the calculation table, another for the feeder and the single-line diagram, and a last one for earthing, bathroom and documentation. Finishing one section a day is more effective than trying to do everything in one afternoon.