← कोर्स पर वापस जाएँ: Spanish Low-Voltage Electrotechnical Regulation (REBT), complete

Overvoltages and direct and indirect contact (ITC-BT-23 and 24)

वीडियो जल्द आ रहा है

Besides overcurrents, an installation must be protected against transient overvoltages, such as those caused by nearby lightning or a network switching, and people against contact with live parts. These are two of the most important topics in the regulation because some affect equipment and others human lives.

Overvoltages (ITC-BT-23)

The regulation classifies equipment into overvoltage categories (I to IV) according to sensitivity and position in the installation, with impulse withstand voltages of 1.5 kV, 2.5 kV, 4 kV and 6 kV on 230/400 V networks. Sensitive electronic equipment is category I or II; equipment at the origin of the installation, category IV. The ITC says when protection with surge protective devices is needed and how to choose it: consult the current ITC.

text
Categoría / Category   Tensión de impulso / Impulse
  I    equipos muy sensibles (electrónica)      1,5 kV
  II   electrodomésticos                        2,5 kV
  III  equipos de instalación fija (cuadros)    4 kV
  IV   origen de la instalación (contadores)    6 kV

Direct contacts (ITC-BT-24)

To avoid contact with live parts, passive measures are applied: insulation of live parts, enclosures or barriers with sufficient protection degree, and placing out of reach. A socket with shuttered contacts, a cable with an insulating sheath and a panel with a cover are everyday examples. As a complementary measure the high-sensitivity RCD (30 mA) is used, which reduces the risk if someone does touch a live part.

Indirect contacts

If an appliance's insulation fails and its metal casing becomes live, a person touching it receives a shock. Protection consists of connecting the casing to earth through the protective conductor and installing a device that automatically cuts the supply when the fault occurs: an RCD. In dwellings, the TT scheme is based on the earth resistance times the RCD trip current being less than the limit contact voltage.

text
Esquema TT:  R_tierra x I_dif <= U_limite   (50 V general, 24 V locales húmedos)
  I_dif = 30 mA, U = 50 V -> R <= 1667 ohm       U = 24 V -> R <= 800 ohm
  • Direct: insulation, enclosures, barriers, distance + 30 mA RCD as reinforcement.
  • Indirect: earth + automatic cut-off (RCD).
  • Wet locations: limit voltage of 24 V.

Practical case

In a house with the washing machine in the garage, the heating element insulation deteriorates and the metal casing ends up at about 100 V relative to earth. With no protective conductor or RCD, nobody notices until someone touches the washing machine with a wet floor. With earthing and a 30 mA RCD, the leakage exceeds the threshold and the RCD opens the circuit within milliseconds, so the user does not even feel the shock. The same fault is dangerous or harmless depending on whether these two protections exist.

Note that the RCD does not prevent the insulation fault, it only prevents its serious consequences. That is why periodic maintenance and checking old appliances remain necessary, and the monthly test button is the cheapest way to confirm that the protection is still active.