← कोर्स पर वापस जाएँ: Spanish Low-Voltage Electrotechnical Regulation (REBT), complete

TT, TN and IT connection schemes (ITC-BT-08)

वीडियो जल्द आ रहा है

Distribution schemes describe how the supply network is earthed and how the exposed parts of the installation are connected. ITC-BT-08 classifies them with two or three letters. The first indicates the position of the supply relative to earth; the second, that of the installation's exposed parts; the third (in TN) indicates whether neutral and protection are the same conductor or separate.

  • T (terre): direct connection to earth. I (isolé): isolated or via impedance.
  • N: exposed parts connected to the supply neutral.
  • TT scheme: neutral earthed at the source and exposed parts to an own earth.
  • TN scheme: exposed parts connected to the transformer neutral (TN-S, TN-C, TN-C-S).
  • IT scheme: isolated supply or via impedance, exposed parts earthed.

What your home uses

Dwellings supplied from the public low-voltage network are usually connected with the TT scheme: the distributor has the neutral of its transformer earthed, and the user has an own earth connection to which the exposed parts are connected. That is why protection against indirect contact depends on the user's earth and on RCDs. In installations with their own transformer substation, such as industry, TN or IT may be used, with other protection rules.

text
TT : neutro a tierra (distribuidora)   masas a TIERRA PROPIA del usuario  -> viviendas
TN : masas al neutro del transformador (TN-S: N y PE separados; TN-C: PEN común)
IT : alimentación aislada; masas a tierra; primer fallo no corta (vigilar)

Protection conditions per scheme

In TT, protection requires the device to cut off when the contact voltage exceeds the limit: R_earth · I_diff ≤ U_limit, with RCDs. In TN, the fault current is high because it returns through the protective conductor; an overcurrent device that cuts within the required time is enough, but an RCD is advisable as well. In IT, the first fault does not cause a trip: it is monitored with an insulation monitoring device and corrected before a second fault occurs, useful in operating theatres and continuous processes.

text
Ejemplo TT:  Rt = 40 ohm, I_dif = 30 mA, U_limite = 50 V
  Rt * I_dif = 40 * 0,03 = 1,2 V <= 50 V  -> cumple

Practical case: a small company receives three-phase supply from the public network and builds a unit with a TT installation. The installer uses 300 mA RCDs at the head for fire protection and 30 mA on socket circuits, office panels and bathrooms. The measured earth resistance is 18 Ω, far from the 167 Ω limit a 300 mA RCD would require with 50 V, and the whole complies with plenty of margin.

✎ मेरे नोट्स

केवल इस ब्राउज़र में सहेजा गया। खाते में रखने के लिए साइन इन करें।0/5000 अक्षर

← पिछलाअगला →