Project: data, electrification grade and circuits
In the first two lessons of this week we solve a complete example together, and in the third you submit your own project with different data. We start with what is always done first: collect the data, decide the electrification grade and define the circuits. The whole process follows what you have studied, in the order a designer would do it.
Example brief
VIVIENDA EJEMPLO
Superficie útil: 105 m2, planta única
3 dormitorios, 2 baños, salón-comedor, cocina
Cocina: placa de inducción + horno (5400 W previstos en C3)
Lavadora, lavavajillas y termo eléctrico (C4)
Aire acondicionado split en el salón: 2500 W
Esquema TT, suministro monofásico 230 V, derivación individual de 20 mStep 1: electrification grade
Electric air conditioning is a criterion that takes the dwelling to elevated electrification, and ITC-BT-25 provides a specific circuit for it (C9). We therefore decide on elevated electrification: minimum design power of 9200 W at 230 V, i.e. 40 A. Although the user may contract less power, the installation is designed for this grade. If the floor area exceeded the ITC threshold, the conclusion would be the same by another route.
Step 2: circuits
C1 Iluminación 1500 W previstos
C2 Tomas generales + frigorífico 3450 W
C3 Cocina y horno 5400 W
C4 Lavadora, lavavajillas, termo 3450 W
C5 Baño y auxiliares de cocina 3450 W
C9 Aire acondicionado 2500 W
(potencias de la ITC-BT-25 orientativas: consultar la tabla vigente)We check whether any additional circuit is needed. With 105 m², three bedrooms and a large living room, a single sockets circuit C2 may fall short of points of use according to the ITC table; if the count exceeds the limit, C7 is added. We count per room: the living room and the three bedrooms, plus hallway and bathrooms. For the example we assume the count complies with C2 and C7 is not needed, although you will check it in your project with the current ITC.
Step 3: total power and simultaneity
The sum of the design powers is 1500 + 3450 + 5400 + 3450 + 3450 + 2500 = 19,750 W. That figure is not the real demand, because no user switches everything on at once: the 9200 W design power of the elevated grade already incorporates a reasonable simultaneity. That is why we do not size the individual feeder with 19.75 kW, but with the grade's design power and, if more is contracted, with the contracted power.
Suma bruta: 19 750 W Previsión grado elevado: 9 200 W -> I = 40 A
IGA >= 40 A DI dimensionada para 40 ACommon mistakes in this phase
The most frequent mistake when starting a project is skipping the electrification grade and calculating directly with the power the client believes is needed. Another is forgetting an additional circuit by not counting the points of use. A third is mixing design power with contracted power: they are different concepts, and the installation must be designed for the grade's design power even if less is contracted today, because changing the contracted power is a cheap procedure and changing the cables is not.