Voltage drop and week review
A cable has resistance, so when current flows the voltage decreases along it. That decrease is the voltage drop. If it is excessive, lamps shine less, motors start badly and appliances can fail. The regulation limits the maximum voltage drop, and it is a sizing criterion as important as heating, especially in long circuits.
Limits
In interior installations supplied from their own panel, the maximum voltage drop from the origin of the installation is 3 % for lighting and 5 % for other uses. On 230 V these are 6.9 V and 11.5 V respectively. In service-connection installations the limits are considerably lower, as we saw in week 3. Consult the current ITC for particular cases.
Formulas
Monofásico: e = 2 * L * I * cos(phi) / (gamma * S) [V]
Trifásico: e = sqrt(3) * L * I * cos(phi) / (gamma * S) [V]
Sección: S = 2 * L * I * cos(phi) / (gamma * e_max) (monofásico)
L en m, I en A, S en mm2, gamma(Cu, 70 C) = 48 m/(ohm*mm2)Single-phase example: a general-socket circuit of 2.5 mm² and 30 m length with 16 A design current. The drop is e = 2 · 30 · 16 / (48 · 2.5) = 960 / 120 = 8 V, i.e. 3.48 % of 230 V. It meets the 5 % limit but would not meet the 3 % limit for lighting. If the same circuit were lighting with 6 A, e = 2 · 30 · 6 / (48 · 1.5) = 5 V = 2.17 %, which does meet the 3 %.
e% = e / 230 * 100
2,5 mm2, 30 m, 16 A -> 8,0 V = 3,48 % (otros usos: <= 5 % OK)
1,5 mm2, 30 m, 6 A -> 5,0 V = 2,17 % (alumbrado: <= 3 % OK)How to choose the cross-section
An orderly procedure: first calculate the design current Ib; then choose the minimum cross-section for heating (corrected current capacity greater than Ib); next calculate the voltage drop and, if it exceeds the limit, increase the cross-section until it complies; finally coordinate the breaker with the cable (Ib ≤ In ≤ Iz). This sequence avoids forgetting a criterion.
- 1. Calculate Ib.
- 2. Cross-section for heating (corrected Iz >= Ib).
- 3. Voltage drop (<= 3 % or 5 %).
- 4. Breaker: Ib <= In <= Iz.
- 5. Check conduit and accessories.
Summary of week 4: colours are a safety protocol, 450/750 V copper is the standard in dwellings, current capacity depends on the installation and is corrected for grouping, and voltage drop is limited to 3 % in lighting and 5 % in other uses. With these pieces you can already size a complete circuit.