Project: cross-sections, protections and individual feeder
With the circuits defined, we move on to the calculations. For each one we apply the week 4 procedure: design current, cross-section for heating, voltage drop and protection Ib ≤ In ≤ Iz. We use the indicative B1 table values and γ = 48; in your real project you must replace them with those of the current ITC.
Circuit calculation table
Circ P(W) Ib(A) L(m) S(mm2) Iz(A) e(V) e(%) PIA(A) Cumple
C1 1500 6,5 22 1,5 15 3,97 1,73 10 Ib<=In<=Iz, e<=3 %
C2 3450 15,0 28 2,5 21 7,00 3,04 16 Ib<=In<=Iz, e<=5 %
C3 5400 23,5 9 6 36 1,47 0,64 25 Ib<=In<=Iz, e<=5 %
C4 3450 15,0 12 4 27 1,88 0,82 20 Ib<=In<=Iz, e<=5 %
C5 3450 15,0 14 2,5 21 3,50 1,52 16 Ib<=In<=Iz, e<=5 %
C9 2500 10,9 16 6 36 1,21 0,53 25 Ib<=In<=Iz, e<=5 %Check one calculation by hand to understand the table. In C2: Ib = 3450 / 230 = 15 A. The 2.5 mm² cross-section carries about 21 A, greater than 15 A. The voltage drop is e = 2 · 28 · 15 / (48 · 2.5) = 840 / 120 = 7 V, which is 3.04 % of 230 V and meets 5 %. The chosen breaker is 16 A, which meets 15 ≤ 16 ≤ 21. The 28 m C2 circuit is close to its reasonable length limit: if the real route were longer, the cross-section would have to go up.
Individual feeder and IGA
The individual feeder carries the design current (40 A) over 20 m. With the 6 mm² minimum cross-section, e = 2 · 20 · 40 / (48 · 6) = 1600 / 288 = 5.56 V, which is 2.4 % of 230 V and exceeds the indicative 1.5 % limit. With 10 mm² we get e = 1600 / 480 = 3.33 V = 1.45 %, which just complies; with 16 mm² we get e = 2.08 V = 0.9 %, with good margin. We choose 16 mm², because the cost difference is small and it leaves room for future extensions.
DI: I = 40 A, L = 20 m, gamma = 48
6 mm2 -> 5,56 V (2,42 %) NO
10 mm2 -> 3,33 V (1,45 %) justo
16 mm2 -> 2,08 V (0,90 %) SI <- elegida
IGA 40 A (9200 W / 230 V)RCDs and panel
[ICP] -> [IGA 40 A] -+- [Dif A 40 A / 30 mA] -- C1(10 A) C2(16 A) C5(16 A)
+- [Dif A 40 A / 30 mA] -- C3(25 A) C4(20 A)
+- [Dif A 40 A / 30 mA] -- C9(25 A)
Limitador de sobretensiones: valorar según ITC-BT-23We split the six circuits among three type A 30 mA RCDs: sockets and lighting on one, cooking and washing on another, and the air conditioning on the third. That way a leak in the air conditioner does not leave the house without lighting and a washing-machine fault does not switch off the fridge. The current ITC-BT-25 states the maximum number of circuits per RCD; check it.
A good habit is to close the calculation with a materials summary: metres of each cross-section, number of breakers per rating, RCDs and conduits. It need not be exact, but it lets the installer quote and the client understand the scope. It also helps discover mistakes: if you get 300 m of 6 mm² cable for a 105 m² dwelling, something is wrong in the lengths you assumed.