Equipotential bonding, earth measurements and review
Connecting exposed parts to earth is not enough if there are other metallic parts, such as water, gas or heating pipes, that may be at a different potential. Equipotential bonding joins all those conductive parts so that, if a voltage appears, they all rise together and there is no dangerous difference between two parts a person could touch at the same time.
Main and local equipotential bonding
The main equipotential bonding is made at the origin of the installation, joining to the earth bar the incoming metal pipes, the building's metal structures and ducts. Local or supplementary equipotential bonding is applied in higher-risk areas, such as the bathroom, where accessible metal parts (bath, pipes, frames) are joined together with conductors of suitable cross-section: consult the current ITC for the cross-sections and the parts to connect.
Barra de tierra principal
|- conductor de tierra -> electrodo
|- PE de circuitos -> masas de aparatos
|- equipotencial -> tuberías de agua / gas / calefacción / estructuraMeasuring the earth
Earth resistance is measured with an earth tester, with the electrode disconnected from the installation at the earthing point and with auxiliary rods placed at a distance. To check the overall protection there are also the measurement of the fault loop impedance and the RCD tripping test with a tester. These measurements form part of the initial verification and periodic checks.
- Earth resistance: earth tester.
- PE continuity: low-resistance ohmmeter.
- Insulation: megohmmeter at 500 V DC.
- RCD tripping: dedicated tester.
- Record the values in the certificate.
Week review
Week 6 in a few lines: earth is built with electrodes (rods, rings, plates) and connected to an accessible point; its resistance must satisfy R · I_diff ≤ U_limit; in dwellings the usual scheme is TT; equipotential bonding avoids potential differences between metal parts, and earth is measured with an earth tester. Everything we have seen will be applied to dwellings in week 7.
Resumen numérico / Numeric summary
30 mA y 50 V -> R <= 1667 ohm 30 mA y 24 V -> R <= 800 ohm
pica: R = rho/L conductor: R = 2 rho/L placa: R = 0,8 rho/PPractical case: renovated bathroom
In a bathroom renovation a metal bath is replaced by a resin one and the copper pipes are replaced by plastic pipework. It seems there are no longer metal parts to connect, but the metal window frame, the towel radiator and the section of copper pipe emerging from the wall remain. Each of those parts that is accessible and conductive must be part of the local equipotential bonding, or otherwise be out of reach. Checking this before laying the tiles avoids opening the wall afterwards.
A last study tip: draw a sketch of the bathroom with the metal parts, indicate which ones you would connect and with what minimum cross-section, and compare it with what the current ITC-BT-27 says. Practising on a concrete case fixes the rules far better than reading them straight through.