← Zurück zum Kurs: Spanish Low-Voltage Electrotechnical Regulation (REBT), complete

Electrical quantities and Ohm's law

Video folgt in Kürze

To read the REBT fluently you need four quantities. Voltage (V, volts) is the 'pressure' that pushes charges; current (I, amperes) is the amount of charge flowing; resistance (R, ohms) is what opposes the flow; and power (P, watts) is the energy per second being converted. They are all linked by two very simple formulas you will use hundreds of times.

text
Ley de Ohm / Ohm's law:     V = I · R
Potencia / Power:          P = V · I
De ahí / hence:            P = I² · R = V² / R

Example: an oven

A 2300 W oven connected to 230 V draws I = P / V = 2300 / 230 = 10 A. Its equivalent resistance is R = V / I = 230 / 10 = 23 Ω. Note that the current is what heats the cables, which is why both protections and cross-sections are chosen from the current, not directly from the watts.

text
I = P / V = 2300 W / 230 V = 10 A
R = V / I = 230 V / 10 A  = 23 ohm

Single-phase and three-phase

In single-phase AC the active power is P = V · I · cos φ, where cos φ is the power factor (1 for a pure resistance such as a heater; lower for motors). In three-phase with line-to-line voltage U = 400 V, P = √3 · U · I · cos φ. With U = 400 V and cos φ = 1, a 6900 W three-phase load draws I = 6900 / (1.732 · 400) ≈ 10 A per phase.

  • Single-phase (dwelling): 230 V between phase and neutral.
  • Three-phase: 400 V between phases, 230 V between phase and neutral.
  • Frequency in Spain: 50 Hz.
  • cos φ = 1 for resistive loads.

Finally, remember energy: it is measured in kWh and is power multiplied by time. A 2.3 kW oven running for one hour uses 2.3 kWh. The bill depends on energy, but the sizing of the installation depends on the maximum power and current.

Common mistakes with the quantities

A classic mistake is confusing power with energy: a 2000 W appliance does not 'spend 2000 W' but, while running, converts 2000 joules every second. Another is forgetting that the total current of a circuit is the sum of the currents of the appliances connected in parallel, which is why a power strip with five heating appliances can exceed the cable limit even if each appliance on its own is reasonable.

text
Ejemplo / Example:
  plancha 2000 W -> 8,70 A
  secador 1800 W -> 7,83 A
  radiador 1500 W -> 6,52 A
  total = 23,05 A  (supera un circuito de 16 A / exceeds a 16 A circuit)

This kind of calculation is the basis of load estimation, which we will study in week 3. There you will see that the regulation does not add up all possible power but applies simultaneity factors: it is unlikely that all appliances run at once, but you must ensure that the installation withstands reasonable use cases.

✎ Meine Notizen

Nur in diesem Browser gespeichert. Melde dich an, um es im Konto zu behalten.0/5000 Zeichen

← ZurückWeiter →