Conductors, colours and insulation (ITC-BT-19)

Video folgt in Kürze

ITC-BT-19 sets out the general requirements for interior or receiving installations: which conductors are used, how they are identified, what insulation they carry and how they are installed. It is one of the most consulted ITCs, because almost every site decision goes through it: what colour each wire is, what minimum cross-section a circuit carries or how much the voltage may drop.

Colour identification

Conductors are identified by the colour of their insulation, and this identification prevents accidents. Neutral is light blue, the protective conductor is green-yellow, and the phase conductors are brown, black or grey. Green-yellow must never be used for any other function, nor light blue for a phase. In three-phase each phase carries one of the three permitted colours.

text
FASE 1: marrón / brown     FASE 2: negro / black     FASE 3: gris / grey
NEUTRO: azul claro / light blue
PROTECCIÓN (PE): verde-amarillo / green-yellow

Insulation and rated voltage

Conductors in interior installations in dwellings are copper, with insulation rated at least 450/750 V. In public-assembly premises and other cases, the rules require low-smoke, halogen-free cables, because in a fire toxic smoke is more dangerous than flame. General-use single-core cables are identified with standardised designations such as H07V-K (PVC) or ES07Z1-K (halogen-free), which refer to UNE standards.

  • Material: copper in dwellings.
  • Minimum rated insulation voltage: 450/750 V.
  • Halogen-free cables in public-assembly premises (ITC-BT-28).
  • Flexible (-K) for panel and conduit wiring.

Minimum cross-sections and connections

Each circuit has a minimum cross-section that depends on its function (for example, 1.5 mm² for lighting and 2.5 mm² for general sockets in dwellings). Connections are always made with terminals, blocks or suitable connectors inside boxes, never by twisting the wires and wrapping them in tape. Junction boxes must be accessible, and splices are not made inside conduits. Protective conductors always accompany the circuit they protect.

text
Mínimos orientativos en vivienda / Indicative housing minimums:
  alumbrado C1: 1,5 mm2   tomas C2: 2,5 mm2   cocina C3: 6 mm2
  lavadora C4: 4 mm2      baño/aux. C5: 2,5 mm2

Practical case: during a refurbishment, an electrician uses the blue wire as a phase to 'save cable'. Years later, another person replaces a socket assuming blue is neutral and gets a shock with the circuit 'off' from a single-pole switch. Colours are not decoration: they are a safety protocol shared among everyone who works on the same installation over decades.