Dwelling circuits (ITC-BT-25)
ITC-BT-25 is the most practical instruction for anyone working on dwellings: it defines the minimum interior circuits, their electrical characteristics and the number of points of use per room. The underlying idea is to split uses into independent circuits: that way a fault in the washing machine does not black out the whole house, and each cable is sized for its real load.
Basic electrification: five circuits
C1 Iluminación PIA 10 A 1,5 mm2 tubo 16 mm
C2 Tomas uso general y frigorífico PIA 16 A 2,5 mm2 tubo 20 mm
C3 Cocina y horno PIA 25 A 6 mm2 tubo 25 mm
C4 Lavadora, lavavajillas y termo PIA 20 A 4 mm2 tubo 20 mm
C5 Baño y auxiliares de cocina PIA 16 A 2,5 mm2 tubo 20 mm
(valores orientativos: consultar la tabla vigente de la ITC-BT-25)Each room has a minimum number of light points, general sockets and switches set by ITC-BT-25: consult the current table. In practice a minimum per room and per floor area is met (for example, more sockets in the living room than in a small bedroom) and sockets are added for chargers, television and data.
Additional circuits
- C6: additional lighting.
- C7: additional general sockets.
- C8: electric heating (25 A breaker, 6 mm²).
- C9: air conditioning (25 A breaker, 6 mm²).
- C10: tumble dryer (16 A breaker, 2.5 mm²).
- C11: automation, energy management and security.
- C12: more C3- or C4-type circuits if needed.
Additional circuits appear according to floor area and equipment. For example, a second lighting or general-socket circuit is added when certain numbers of points or area are exceeded; the ITC defines the thresholds. The logic is that no circuit ends up with too many loads.
Panel protection
The panel has an all-pole main circuit breaker of at least 25 A, one or more 30 mA RCDs (each protects a limited number of circuits; check the current ITC), one breaker per circuit and, when ITC-BT-23 requires it, surge protection. The protective conductor accompanies all circuits and all socket outlets have an earth contact.
Comprobación de C4: lavadora 2300 W + termo 1500 W = 3800 W
Ib = 3800/230 = 16,5 A <= PIA 20 A <= Iz(4 mm2 ~ 27 A) OKPractical case: an owner wants to add a 3 kW air conditioner to a flat. If there is no free C9 circuit, it must not be hung from a general socket (C2, 16 A, 2.5 mm²): 3000 W is 13 A of continuous load, which together with other appliances would exceed the breaker. The correct way is to create a dedicated C9 circuit with a 25 A breaker and 6 mm², and to check that the contracted power and the IGA allow it.
One last design nuance: always leave some spare capacity in the panel (free slots to add a breaker or an RCD) and leave spare conduits in difficult passages. Extending a well-thought-out installation costs a fraction of redoing a badly conceived one, and most dwellings add over the years new appliances that were not foreseen.
✎ Мои заметки
Сохранено только в этом браузере. Войдите, чтобы хранить в аккаунте.0/5000 символов