Current capacity and installation systems (ITC-BT-19, 20 and 21)

動画は近日公開

A cable heats up when current flows through it: the more current and the smaller the cross-section, the more heat. Current capacity is the maximum current a cable can carry continuously without exceeding its limit temperature. It depends on the cross-section, the material, the insulation and how it is installed, because a cable in free air cools better than one surrounded by others inside a wall.

Installation methods

ITC-BT-19 classifies installation ways into reference methods identified by letters: for example, conductors in conduit embedded in an insulating wall, in conduit on a wall or on a tray. Each method has its column in a table of current capacities, which refers to a UNE standard. Here we will use indicative values to understand the procedure, always remembering that in a real project you must consult the current ITC table.

text
Valores orientativos (PVC, 2 conductores cargados, Cu, método B1: tubo sobre pared)
  1,5 mm2 -> 15 A    2,5 mm2 -> 21 A    4 mm2 -> 27 A    6 mm2 -> 36 A    10 mm2 -> 50 A
SIEMPRE: consultar la tabla vigente de la ITC-BT-19

Correction factors

The table values apply under reference conditions. If several circuits share a conduit or trunking, or if the ambient temperature is high, correction factors must be applied that reduce the current capacity. That is why a conduit with four loaded circuits carries less current per cable than a single circuit. The circuit design current must be less than or equal to the corrected capacity.

text
Ib <= Iz_corregida = Iz_tabla x f_agrupamiento x f_temperatura
Ejemplo: 6 mm2 (36 A) con factor 0,8 -> 28,8 A  (sirve para un circuito de 25 A)

Conduits and trunking (ITC-BT-20 and 21)

Conductors are housed in conduits (rigid, bendable or flexible, embedded or surface-mounted), protective trunking or trays. ITC-BT-21 sets the minimum conduit diameter according to the number and cross-section of the conductors: the conduit must not be full so that cables can be pulled and heat can dissipate. In dwellings the diameters per circuit (16, 20, 25 mm...) appear in ITC-BT-25: consult the current ITC.

  • Embedded conduits: protect and allow cables to be replaced.
  • Surface trunking: easy to extend.
  • Trays: for many cables in technical or industrial premises.
  • Minimum bending radii so as not to damage cables.

Practical procedure: calculate the circuit current, choose a cross-section that, after correction, has a higher current capacity, and then check the voltage drop (next lesson). Finally check that the breaker rating protects that cable: In cannot exceed the corrected capacity.