Overcurrent protection (ITC-BT-22)
An overcurrent is a current greater than expected. It may be an overload, which is a moderate, prolonged excess in a healthy circuit, or a short circuit, which is an enormous current caused by a very-low-impedance connection between conductors. ITC-BT-22 requires protecting every circuit against both cases with circuit breakers or fuses, so that the cable does not heat up to the point of damaging its insulation and causing a fire.
Overload protection
Two conditions are checked. The first: Ib ≤ In ≤ Iz, i.e. the circuit design current (Ib) does not exceed the device rating (In), and that does not exceed the cable current capacity (Iz). The second: the current that ensures the device operates within the conventional time (I2) does not exceed 1.45 times Iz. For modern circuit breakers, the second condition is met automatically if the first is met, because I2 equals 1.45 In.
Ib <= In <= Iz (1)
I2 <= 1,45 * Iz (2) interruptor automático: I2 = 1,45 In -> (2) se cumple si In <= Iz
Ejemplo C2: Ib = 14 A, PIA In = 16 A, cable 2,5 mm2 Iz = 21 A -> 14 <= 16 <= 21 OKShort-circuit protection
A short circuit must be cleared so fast that the cable does not reach its limit temperature. For that the device must have a breaking capacity equal to or greater than the maximum prospective short-circuit current at its point of installation, and its tripping time must be shorter than the time the cable takes to be damaged. In a dwelling fed from the public network, a breaking capacity of 4.5 kA or 6 kA is usual for breakers; always check the short-circuit value the distributor gives you.
- Curve B: magnetic trip between 3 and 5 times In (long cables, little inrush).
- Curve C: between 5 and 10 times In (general use in dwellings).
- Curve D: between 10 and 20 times In (motors and transformers with strong starting).
Icc aproximada (monofásico) = U / Z_bucle
Ej.: Z_bucle = 0,4 ohm -> Icc = 230 / 0,4 = 575 A (el PIA C16 dispara con 80 a 160 A: OK)Where protections are placed
The protection is placed at the origin of the circuit, where the cross-section or nature of the cable changes. There are very specific exceptions in the ITC, but in a dwelling each circuit leaves from a breaker in the panel and cross-section reductions are not inserted without another protection. It is also advisable that the device be all-pole or that the main switch cuts phase and neutral.
Practical case: on a 2.5 mm² circuit with a 16 A breaker two 2000 W heaters are connected. The current is 4000 / 230 = 17.4 A, above 16 A, and the breaker ends up tripping after a few minutes. A quick fix would be to fit a 25 A breaker, but the 2.5 mm² cable only handles about 21 A: it would overheat with nothing to cut it off. The correct solution is to spread the heaters across different circuits or install a dedicated circuit with the right cross-section.