RCDs, protection coordination and review
The residual current device compares the current entering through the phase with the current returning through the neutral. If the difference exceeds its rated sensitivity, there is a leakage to earth (perhaps through a person) and it opens the circuit within milliseconds. It is the most effective protection against indirect contact and a complementary one against direct contact. This lesson explains which types exist, how they are chosen and how they are coordinated with the rest of the panel.
Sensitivity and rated current
Sensitivity (30 mA, 300 mA...) is the leakage current that causes tripping. In dwellings 30 mA is used, because below that value the shock is not usually fatal if the cut-off is fast. The rated current (25, 40, 63 A) is the load current the device can carry: it must be at least equal to that of the circuits it protects. In a basic dwelling with a 25 A IGA, a 40 A RCD is usually installed.
30 mA -> personas (viviendas, baños, enchufes)
300 mA -> protección contra incendios en cabecera / selectivo
I_nominal diferencial >= corriente de los circuitos que protegeTypes of RCD
RCDs are classified by the waveform of the leakage current they detect. Type AC detects sinusoidal AC leakage. Type A also detects pulsating DC currents, common in appliances with electronics (washing machines, induction hobs, drives). Type F adds immunity in circuits with single-phase drives, and type B also detects smooth DC currents, needed in some applications such as certain electric vehicle charging points. ITC-BT-52 and the manufacturer's instructions say which type is required in each case.
- AC: AC leakage only.
- A: AC + pulsating DC (very common today).
- F: single-phase drives.
- B: smooth DC (some charging points).
Coordination and selectivity
With several RCDs in the panel, a fault in one circuit should only trip the RCD of its group and not the main one. In dwellings the load is split: each RCD protects a limited set of circuits (check the maximum in the current ITC-BT-25), so that if one trips the rest of the house stays lit. In larger installations selective (time-delayed) RCDs are used upstream and instantaneous ones downstream.
[IGA 25 A]
|-- [Dif A 40 A/30 mA] -- C1 C2 C5 (alumbrado, tomas, baño)
|-- [Dif A 40 A/30 mA] -- C3 C4 (cocina, lavadora, termo)Week 5 review: the breaker protects the cable (Ib ≤ In ≤ Iz), the surge protector protects equipment, and the 30 mA RCD protects people. It is tested monthly with its T button. Together with earthing, which we will see next week, they form the core of electrical safety in a dwelling.