Earthing (ITC-BT-18)
Earthing is the direct connection, without protective devices, between certain parts of the installation and the ground. It serves to limit the voltage exposed metal parts can reach relative to the ground, ensure that protective devices act when there is a fault and discharge dangerous currents. ITC-BT-18 regulates how it is designed, built and checked.
Parts of an earthing system
- Electrode: buried part in contact with the ground (rods, plates, buried conductor, foundation ring).
- Earth link line: joins the electrodes to the earthing point.
- Earthing point: accessible terminal or bar, which can be disconnected to measure.
- Main earth line and branches: carry the earth to the exposed parts.
- Protective conductors: accompany each circuit (green-yellow).
Electrode types and their resistance
The resistance of an earth connection depends on the type of electrode and the ground resistivity (ρ, in Ω·m), which varies greatly with moisture and composition. The indicative formulas in ITC-BT-18 are simple: for a vertical rod of length L, R ≈ ρ / L; for a horizontal buried conductor of length L, R ≈ 2ρ / L; for a plate of area P, R ≈ 0.8 ρ / P. Resistivity values must be taken from tables or measured; consult the current ITC.
Pica (rod): R = rho / L rho = 100 ohm*m, L = 2 m -> R = 50 ohm
Conductor (buried):R = 2*rho / L rho = 100, L = 20 m -> R = 10 ohm
Placa (plate): R = 0,8*rho / P rho = 100, P = 0,5 m2 -> R = 160 ohmFoundation ring
In new buildings a bare copper conductor is laid at the bottom of the foundation trench forming a perimeter ring, with rods if needed. This large-surface electrode in contact with reinforced concrete offers low, stable resistances and is connected to an accessible earthing point. In renovations and old houses the earth may consist of independent rods or may even be missing: in that case it has to be built.
Practical case: a detached house has a 30 mA RCD and a 50 V limit voltage, i.e. it needs an earth resistance below 1667 Ω. With a 2 m rod in 100 Ω·m ground, R = 50 Ω: it complies with plenty of margin, even if the ground dries out and resistivity multiplies by five (250 Ω). Even so a much lower value is preferred because it reduces the actual contact voltage during a fault.
Comprobación / Check: R_tierra x I_dif <= 50 V
50 ohm x 0,03 A = 1,5 V << 50 V (seco: 250 x 0,03 = 7,5 V)One more detail: rods should be connected with exothermic welding or specific clamps, never with simply twisted wires, because the joint must keep its low resistance for decades underground, in moisture and corrosion.